Device Config Templates¶
This page lists the currently supported deviceConfig templates for common EPICS-backed device classes exposed through ophyd_devices.
EPICS motor classes¶
ophyd_devices.EpicsMotor¶
deviceConfig fields:
prefix:str, required. EPICS IOC prefix, for exampleX25DA-ES1-MOT:limits:tuple[float, float] | None, optional. Soft limits of the motor
Full example:
samx:
readoutPriority: baseline
description: Beamline sample stage X motor
deviceClass: ophyd_devices.EpicsMotor
deviceConfig:
prefix: 'X25DA-ES1-MOT:'
deviceTags:
- motor
onFailure: retry
enabled: true
readOnly: false
softwareTrigger: false
ophyd_devices.EpicsMotorEC¶
deviceConfig fields:
prefix:str, required. EPICS IOC prefix, for exampleX25DA-ES1-MOT:limits:tuple[float, float] | None, optional. Soft limits of the motor
Full example:
samx_ec:
readoutPriority: baseline
description: ECMC-based sample stage X motor
deviceClass: ophyd_devices.EpicsMotorEC
deviceConfig:
prefix: 'X25DA-ES1-MOT:'
deviceTags:
- motor
onFailure: retry
enabled: true
readOnly: false
softwareTrigger: false
ophyd_devices.EpicsUserMotorVME¶
deviceConfig fields:
prefix:str, required. EPICS IOC prefix, for exampleX25DA-ES1-MOT:limits:tuple[float, float] | None, optional. Soft limits of the motor
Full example:
samx_vme:
readoutPriority: baseline
description: VME user motor for sample stage X
deviceClass: ophyd_devices.EpicsUserMotorVME
deviceConfig:
prefix: 'X25DA-ES1-MOT:'
deviceTags:
- motor
onFailure: retry
enabled: true
readOnly: false
softwareTrigger: false
EPICS signal classes¶
ophyd_devices.EpicsSignal¶
deviceConfig fields:
read_pv:str, required. EPICS read PV, for exampleX25DA-ES1-MOT:GETwrite_pv:str | None, optional. EPICS write PV if it differs fromread_pv
Full example:
beamstop_open:
readoutPriority: monitored
description: Beamstop open state
deviceClass: ophyd_devices.EpicsSignal
deviceConfig:
read_pv: 'X25DA-ES1-OP:OPEN'
write_pv: 'X25DA-ES1-OP:OPEN'
deviceTags:
- signal
onFailure: retry
enabled: true
readOnly: false
softwareTrigger: false
ophyd_devices.EpicsSignalRO¶
deviceConfig fields:
read_pv:str, required. EPICS read PV, for exampleX25DA-ES1-MOT:GET
Full example:
ring_current:
readoutPriority: monitored
description: Storage ring current
deviceClass: ophyd_devices.EpicsSignalRO
deviceConfig:
read_pv: 'ARIDI-PCT:CURRENT'
deviceTags:
- signal
onFailure: retry
enabled: true
readOnly: true
softwareTrigger: false
ophyd_devices.EpicsSignalWithRBV¶
deviceConfig fields:
prefix:str, required. EPICS IOC prefix, for exampleX25DA-ES1-DET:ACQUIRE
Full example:
detector_acquire:
readoutPriority: monitored
description: Detector acquire state
deviceClass: ophyd_devices.EpicsSignalWithRBV
deviceConfig:
prefix: 'X25DA-ES1-DET:ACQUIRE'
deviceTags:
- signal
onFailure: retry
enabled: true
readOnly: false
softwareTrigger: false
Notes¶
- The examples show complete device entries so you can see how
deviceConfigfits into the wider BEC config structure. - The only class-specific part documented here is
deviceConfig. Top-level fields such asreadoutPriority,deviceTags,enabled, andreadOnlyare shared BEC config fields. - The field names and types here are based on the current local
ophyd_devicesconfig templates.